Category:Dry Type Transformer
Phase: Three Phase
Primary Voltage Ratings: 15KV - 22KV or Custom
Secondary Voltage Ratings: 200v-440v or Custom
Rated Capacity: 30-3000KVA or Custom
Rated Frequency: 50/60HZ
Materials: Copper / Aluminum
The 20KV SCB10 series dry-type transformers meets various standards. It has been proved by users to operate reliably and reach the advanced level.
This series of products adopt foreign advanced manufacturing technology, complete, correct and fresh design drawings and technical documents, advanced production equipment, stable manufacturing technology, and complete measurement methods, which provide a solid guarantee for the production of high-quality products.
SCB 10(11)Series 20kV level resin insulation dry-type power transformers technical parameters | ||||||||||
Rated Capacity KVA |
Voltage Combination | Vector group |
No-load Loss(W | No-load current (%) |
Impedance (%) |
under the different insulation heat-resisting rank load loss(w) |
||||
30℃(B) (100℃) |
155℃(F) 120℃) |
180℃(H 145℃) |
||||||||
High Voltage (KV) |
Tapping Range (%) |
Low Voltage (KV) |
||||||||
50 | 20 22 24 |
±5 or ±2x2.5 |
0.38 0.4 0.415 0.433 |
Dyn11 or Yyn0 |
340 | 2 | 6 | 340 | 1230 | 1310 |
100 | 540 | 1.8 | 540 | 1990 | 2130 | |||||
160 | 670 | 1.6 | 670 | 2470 | 2690 | |||||
200 | 730 | 1.6 | 730 | 2940 | 3140 | |||||
250 | 840 | 1.3 | 840 | 3420 | 3660 | |||||
315 | 970 | 1.3 | 970 | 4080 | 4360 | |||||
400 | 1150 | 1.1 | 1150 | 4840 | 5180 | |||||
500 | 1350 | 1.1 | 1350 | 5790 | 6190 | |||||
630 | 1530 | 1 | 1530 | 6840 | 7320 | |||||
800 | 1750 | 1 | 1750 | 8260 | 8840 | |||||
1000 | 2070 | 0.8 | 2070 | 9780 | 10400 | |||||
1250 | 2380 | 0.8 | 2380 | 11500 | 12300 | |||||
1600 | 2790 | 0.8 | 2790 | 13800 | 14800 | |||||
2000 | 3240 | 0.6 | 8 | 3240 | 16300 | 17500 | ||||
2500 | 3870 | 0.6 | 3870 | 19300 | 20700 |